Application and package scope
Receives a position setpoint from the control system and uses actual valve-position feedback to adjust pneumatic output, moving the actuator towards the target. A positioner is a control accessory, not the driving air supply or a complete control valve with body and actuator.
Configuration options and purchasing checks
| Item | Configuration |
|---|---|
| Typical control input | 4–20mA; direct/reverse action and range per configuration |
| Compatible equipment | Compatible linear or part-turn pneumatic actuators |
| Pneumatic output | Select single-acting or double-acting versions separately |
| Valve-position feedback | Separate feedback module, where required |
| Smart functions | HART or diagnostic functions only on supporting versions |
| Air supply and mounting | Specify supply air, filter regulator, bracket and feedback linkage separately |
Control input and feedback output have different directions
The control system sends a setpoint to the positioner; a feedback module returns actual valve position to the system. Do not interchange the connections merely because both use 4–20mA. Check terminal definitions, ranges and signal directions against the actual wiring diagram.
Match output channels to the actuator
Spring-return single-acting actuators and double-acting cylinders require different pneumatic output arrangements. Also check linear or rotary travel, feedback linkage or rotary coupling, air pressure and mounting space; signal range alone is insufficient.
Check pneumatic conditions even when the signal is normal
A positioner does not generate its own motive power. Low air supply, leakage, blocked filtration or abnormal valve resistance can prevent the target position being reached. Qualified personnel must follow equipment instructions and site safety procedures for maintenance.
Enquiry and supply documents
Provide the mating valve, load or service conditions, interface drawing, utility and control requirements, environment and quantity. Jiangsu Tekron Flow Control Valve Co., Ltd. can discuss a suitable configuration on this basis. The final model, accessories, drawings and inspection requirements are subject to the agreed technical specification.
Product photographs illustrate a configuration; not every accessory shown is automatically included. Third-party branding identifies the illustrated accessory. Confirm the brand and model offered separately; the photograph does not imply that this company manufactures the third-party product or owns its trademark.
Related categories:Valve actuators and accessories · Electric actuated valves · Pneumatic valves · Control valves
Selection questions
Can a positioner operate a valve without an air supply?
No. The electrical signal carries the setpoint. Suitable instrument air and the actuator provide the actual pneumatic driving force.
Can a single-acting positioner directly control a double-acting cylinder?
Do not assume interchangeability. Check positioner output channels, actuator action and the pneumatic circuit, and select the matching version.
Does a communication option include feedback and mounting hardware?