Application and package scope
Provides electric drive for valves requiring multiple turns to open and close, commonly gate and globe valves. Selection must address output torque, turns per stroke, output speed, stem connection and the way axial thrust is carried.
Configuration options and purchasing checks
| Item | Configuration |
|---|---|
| Output motion | Multi-turn |
| Main duty | Fully open, fully closed and remote isolation control |
| Power-supply reference | AC220V or AC380V, according to model |
| Mechanical checks | Stem thread, output bore, drive nut and turns per stroke |
| Protection functions | Travel, torque and motor protection per selected arrangement |
| Feedback requirements | Open/closed and fault signals per I/O schedule |
Select turns, speed and torque together
The turns required for full valve travel and actuator output speed jointly determine operating time. Motor power or a single maximum torque figure alone cannot show whether the installed assembly will complete the required process movement.
Check rising-stem and non-rising-stem interfaces separately
Whether the stem passes through the actuator, how the drive nut engages and which component carries thrust depend on the valve design. Provide an interface drawing for replacement. Matching mounting holes alone do not establish assembly interchangeability.
Set stopping criteria from the valve instructions
Travel-dependent and torque-dependent stopping serve different purposes. Select the stopping method for the seat design and assembly instructions. An overload trip is not a normal closed-position signal; verify shut-off tightness separately by testing the complete valve.
Enquiry and supply documents
Provide the mating valve, load or service conditions, interface drawing, utility and control requirements, environment and quantity. Jiangsu Tekron Flow Control Valve Co., Ltd. can discuss a suitable configuration on this basis. The final model, accessories, drawings and inspection requirements are subject to the agreed technical specification.
Product photographs illustrate a configuration; not every accessory shown is automatically included in the supply.
Related categories:Valve actuators and accessories · Electric actuated valves · Pneumatic valves · Control valves
Selection questions
Can a multi-turn actuator directly replace a part-turn actuator?
No. Their output movements differ. An appropriate, matched motion-conversion mechanism is required to form a suitable assembly.
Will a more powerful motor make a slow valve operate faster?
Not necessarily. Check output speed, turns per stroke, reduction gearing, valve load and the operating speed permitted by the process.
Why is a stem-end drawing needed for a multi-turn actuator quotation?
The thread, bore, drive nut and thrust arrangement determine fit and load capacity. Valve size alone does not define them.