Application and package scope
Air pressure drives one direction and springs drive the return stroke, providing a fail-safe action for compatible part-turn valves. Match spring-return direction to the valve design, assembly orientation and process requirements. Single-acting does not automatically mean fail-close.
Configuration options and purchasing checks
| Item | Configuration |
|---|---|
| Action | Single-acting, spring return |
| Rotation reference | Typically 90° part-turn movement |
| Air-supply reference | Typically 0.4~0.7MPa; actual requirements per selected springs and model |
| Fail-safe position | Fail-open or fail-close, according to the complete valve assembly and control design |
| Load checks | Check the air stroke and spring-return stroke separately |
| Accessories | Solenoid valve, end-position feedback, filter regulator and other accessories per supply list |
Both strokes need sufficient torque
The air stroke must overcome both spring and valve loads; springs drive the return stroke. Spring output differs at the start and end of travel. Check torque throughout the stroke, rather than comparing a single peak value.
Air failure and power failure are different conditions
Actuator response to air failure is related to, but different from, the air-circuit state after solenoid power loss. Specify the required responses to power loss, air loss and control-signal loss separately. Validation must cover the actual valve and accessory combination.
Safety functions require assembly-level evidence
Springs alone do not establish a safety integrity level for the complete equipment or guarantee closure in every abnormal condition. For a safety interlock, provide the functional target, failure logic and validation requirements.
Enquiry and supply documents
Provide the mating valve, load or service conditions, interface drawing, utility and control requirements, environment and quantity. Jiangsu Tekron Flow Control Valve Co., Ltd. can discuss a suitable configuration on this basis. The final model, accessories, drawings and inspection requirements are subject to the agreed technical specification.
Product photographs illustrate a configuration; not every accessory shown is automatically included in the supply.
Related categories:Valve actuators and accessories · Electric actuated valves · Pneumatic valves · Control valves
Selection questions
Is it sufficient for the spring to return an unloaded valve?
No. Check available torque throughout the return stroke at the agreed maximum differential pressure, temperature and valve resistance.
Can a single-acting actuator be configured to fail open?
Yes, where supported by the design and complete valve assembly. Check valve rotation, spring direction and the pneumatic circuit documents.
Should power-loss and air-loss actions be checked separately?
Check each according to the project requirements. The de-energized solenoid state and the actuator's mechanical response to air loss must together meet the process objective.